  1. If you look at the schedule object, navigate to...

    If you look at the schedule object, navigate to the scheduled items in the navigation mode. Make sure that the occupied command which is I believe bd227 in the UNT controller is there. If so, then...
  2. Just because you swapped the sensor does not mean...

    Just because you swapped the sensor does not mean the wiring is not bad from the controller to the sensor. If it works in commissioning mode and not in the jace you have a jace issue.
  3. Silly question but did you ohm out the sensor...

    Silly question but did you ohm out the sensor from the wiring at the controller to confirm there are no issues with wiring. This line of controllers is pretty bullet proof to use. Next question, if...
  4. Ended up changing out the PC with Win7-32 bit pro...

    Ended up changing out the PC with Win7-32 bit pro version. No more problems and never did find out what was causing this.
  5. Replies
    9
    Views
    443

    It must be selected as exp 4di4do, it is on the...

    It must be selected as exp 4di4do, it is on the bottom of the selection drop down.
  6. Replies
    9
    Views
    443

    If you selected the xp as xp 4di 4do then you...

    If you selected the xp as xp 4di 4do then you will also need an XT module. If you open up the module for this you will see a configuration for the module in which you need to set an N2 address. IF...
  7. Replies
    9
    Views
    443

    When you selected the second module how dud you...

    When you selected the second module how dud you select it? The first module would be selected as the xp 6a12ao and the second module must be selected as exp......
    If not you are adding another...
  8. Metasys GGT Graphics not displaying on Win XP

    Hello, I am working on a Metasys system with GGT graphics. The issue is one XP machine will not display the graphics, just a plain greay/white screen. If I restart Metasys I might get one GGT...
  9. Replies
    14
    Views
    928

    We have an issue that is similar, we lose...

    We have an issue that is similar, we lose connectivity to the device every few days as out IT dept does maintenance. A firewall reload for instance causes about a 5 minute outage to that device. I...
  10. Replies
    14
    Views
    928

    Are these on a managed network or are they on a...

    Are these on a managed network or are they on a private network? If they are managed check with IT to see if there is something being done with firewall maintenance or some other reload or testing...
  11. Honeywell Solid State Current Valve (SCR)

    Hi All, I am looking for info on this device part# R7425A1017. It is an old Honeywell SCR and cannot find literature online or by contacting Honeywell. It was connected to old H'well controls...
  12. Yes it is.

    Yes it is.
  13. I worked there for 8 years as a Systems Rep, DDC...

    I worked there for 8 years as a Systems Rep, DDC tech. It is a great place to learn and take it for what it is. JCI is a large multi-national company that looks out for its shareholders before...
  14. Replies
    4
    Views
    453

    In MSEA, you can use LCT/Interlock/Global etc. to...

    In MSEA, you can use LCT/Interlock/Global etc. to write to an analogue input as long as it is not on a DX-9100 controller. There are a couple of ways to do it. The most simple is to put the input...
  15. Replies
    0
    Views
    276

    Metasys and Pegasys Integration

    Hello, we have these two integrated together and under the ADX I can see the Pegasys Server and it's points. However, I cannot add extensions to the individual point in order to trend or alarm...
  16. Interfacing Reliable Mach-1 Controller into a JCI NCE controller

    Hello, I have a customer with several sites with Reliable Mach-1 controls with at least one site with a Mach-Global controller. All devices have network enabled communications that he is able to...
  17. Hi, we have over 350 of these in one of our...

    Hi, we have over 350 of these in one of our buildings. We used Johnson VMA controllers, the N2 type, and left the pneumatics in place. We were able to control both the mixing of the hot and cold...
  18. Try this out from Greystone,...

    Try this out from Greystone,
    http://greystoneenergy.com/webcura/files/247807_gt_ares_spec.pdf
  19. Replies
    6
    Views
    1,366

    JCI will sell to a building owner and this is...

    JCI will sell to a building owner and this is part of the SCT tools which would include the database/offline programming tools for the MSEA, HVACpro, GX-9100 and of course the CCT Tools.
  20. Metasys MSEA to Edwards Quick Start Panel Integration

    Looking to integrate the two systems on an LAN as we wish to see all of the devices on the Edwards Quick Start Panel.

    Has anyone done this or have guidance other then using a fieldserver box?
    ...
  21. Replies
    14
    Views
    1,782

    Hi, if you do not have the DX key for the editing...

    Hi, if you do not have the DX key for the editing of paramaters in the DX you can use a small jumper or set of needle nose pliers. The "key" essentially jumps the top and bottom pins of the plug...
  22. Replies
    1
    Views
    526

    It must be brought in through an NAE and a Bacnet...

    It must be brought in through an NAE and a Bacnet integration and the NAE will discover the points.
  23. Replies
    12
    Views
    1,108

    Hi Integrator, check to ensure that IT has not...

    Hi Integrator, check to ensure that IT has not blocked anything. Is the ADS behind a firewall? We have had the same issues but found that IT had to make modifications to all ports for each PC being...
  24. Replies
    9
    Views
    722

    JCI is stopping production of all N2 devices from...

    JCI is stopping production of all N2 devices from that era of controllers. They apparently are replacing them with an FEC that will communicate on the N2.

    Role the dice on this one. The UNT is...
  25. Replies
    2
    Views
    399

    Is there any chance it got added into a schedule?

    Is there any chance it got added into a schedule?
  26. Replies
    9
    Views
    710

    Then map the hours into a graphic or a user view....

    Then map the hours into a graphic or a user view. Right click on the hours and you should be able to reset from there.

    If not, check to see if you have the rights to do this.
  27. Replies
    9
    Views
    710

    Is the runtime calculation being done in an FEC...

    Is the runtime calculation being done in an FEC or through the totalization block in the BI?
  28. Replies
    9
    Views
    710

    Right click on the hours, select reset.

    Right click on the hours, select reset.
  29. Replies
    2
    Views
    515

    FEC's over a dedicated leased line

    Hi all, we have many out buildings where we cannot get a fibre connection and will need a dedicated leased line (phone). I have a requirement to install FEC's to monitor equipment and need to get...
  30. Replies
    28
    Views
    2,379

    One other thing to check since this is being...

    One other thing to check since this is being monitored via a head end device. Check to see if the AO for the cooling valve is under local control. Also, have a look to see if there is possibly some...
  31. Replies
    28
    Views
    2,379

    The sequence should be on the O&M manuals that...

    The sequence should be on the O&M manuals that were left onsite when JCI or the mechanical contractor left onsite.

    You can always contact JCI for a copy of them, they are worth their weight in...
  32. Replies
    28
    Views
    2,379

    Depends on the sequence of operations, I noticed...

    Depends on the sequence of operations, I noticed the OA-T is around the freezing mark which would typically have disabled cooling and enabled heating. This means that the only way to get the supply...
  33. Replies
    28
    Views
    2,379

    Just by looking at the screenshot it looks like...

    Just by looking at the screenshot it looks like the heating valve is passing. 51 off the coolnig coil and 61 or so off the heating coil. Looks like the issue is here.
  34. If the output is not defined in the UNT is will...

    If the output is not defined in the UNT is will not work.
  35. Replies
    3
    Views
    575

    You need to write the Supervisory Schedule to...

    You need to write the Supervisory Schedule to ADI78 which is the scheduled point in the VMA. If the occupancy button is pushed it will override the Occ Mode in the VMA.

    Don't forget that this is...
  36. Replies
    25
    Views
    3,215

    Since you don't have avything left to lose with...

    Since you don't have avything left to lose with this device has you tried the reset button located on the panel?

    This will reset the device back to factory defaults.

    After that, using the steps...
  37. Found the issue, when I replaced the controller I...

    Found the issue, when I replaced the controller I found that water had gotten into the cabinet and onto the back of the circuit board. The corrosion and damage to the board is what did it.
  38. Replies
    7
    Views
    1,225

    SCT is the offline database generation tool. It...

    SCT is the offline database generation tool. It also is the only tool that can backup and restore databases.

    If there is an ADX onsite I would hope that the SCT is loaded on it. You can check by...
  39. Replies
    7
    Views
    1,225

    If you have performed a backup of the database...

    If you have performed a backup of the database from SCT and saved at an earlier date of course you can. You restore the old database in SCT and find the missing graphic.

    The issue with this being...
  40. UNT-110-1 Thinks it is a Pheonix Fume Hood

    I had a UNT110-1 go offline from my NAE and when I went onsite to investigate I found out the UNT thinks it is a fume hood controller. I was able to communicate to it with HVACpro software Ver 8.08B...
  41. Replies
    8
    Views
    618

    The enable alarms in the UNT would have nothing...

    The enable alarms in the UNT would have nothing to do with this issue. Can you command the point from the front end? Are you writing to the point at an appropriate level?
  42. Replies
    8
    Views
    618

    Not familiar enough with the FX-60 but with...

    Not familiar enough with the FX-60 but with Metasys you need to define the analogue input as an analogue output with the address reflecting AI-6.
    The other thing to do is to put the AI out of...
  43. Replies
    14
    Views
    1,991

    Also, try the last 4 digits of the company phone...

    Also, try the last 4 digits of the company phone number.
  44. Thread: JCI NIE

    by Froz'ninWpg
    Replies
    4
    Views
    684

    Yes it is possible. You need the tools from the...

    Yes it is possible. You need the tools from the disk for NAE configuration tool, Update tool, the images as well as pretty much a complete SCT load on a machine.

    The steps for flashing it are the...
  45. Replies
    13
    Views
    914

    Is the shutdown status on? Are the tuning...

    Is the shutdown status on? Are the tuning paramaters in all of the loops properly defined, ie. prop bands and integrals?

    If you like, send me the program email is in my profile and I am at my...
  46. Replies
    13
    Views
    914

    Silly question but is the fan status on? Are all...

    Silly question but is the fan status on? Are all of your input/outputs reading correctly? Is the fan system occupied? Does the system work if you plug into it with HVACPro from you computer and...
  47. Replies
    2
    Views
    338

    Yes it is. Happy New Year.

    Yes it is.

    Happy New Year.
  48. Replies
    3
    Views
    603

    You would use a sideloop for PI control with...

    You would use a sideloop for PI control with reset to BO Sequencer.
  49. Replies
    12
    Views
    694

    Athens, Greece? Loved it there and was hoping to...

    Athens, Greece? Loved it there and was hoping to go back for my upcoming wedding in June but due to the economic turmoil over there we are hesitating.

    Do you have the Metasys.ini file setup to...
  50. Replies
    12
    Views
    694

    Check the uploaded doc.

    Check the uploaded doc.
Results 1 to 50 of 115
Page 1 of 3 1 2 3
Comfortech Show Promo Image

Related Forums

Plumbing Talks | Contractor Magazine
Forums | Electrical Construction & Maintenance (EC&M) Magazine
Comfortech365 Virtual Event