    Matrix. Not disagreeing with what you said. ...

    Matrix. Not disagreeing with what you said. Just trying to understand.

    So if I put one controller and connect it to two JACE all would be OK?
  2. That's the same symptoms I had. I was like half...

    That's the same symptoms I had. I was like half the program was running but other parts were not. A brief power glitch will sometimes cause the controller not to reboot at all or not properly. I...
  3. What capacity are you at with the program size? ...

    What capacity are you at with the program size? I have had this happen with controllers that were at or pushing max recommended capacity. If you are much over 85% capacity then that is most likely...
  4. I'm not much on the mechanical side but most...

    I'm not much on the mechanical side but most Trane units have a set of contacts where you can cycle it thru test mode. All the compressors will fire, fans on and heat if it's set up. You have to...
  5. Depends on the type of unit and how Trane has it...

    Depends on the type of unit and how Trane has it setup. Looks as though Type A is space temp control. Make sure your occ and unocc setpoints are in the correct order. Looks like Type B is doing...
  6. Replies
    32
    Views
    977

    Hooking the FX 60 to the device probably wasn't...

    Hooking the FX 60 to the device probably wasn't the best of ideas. LON can only have one managing device. In this case it was the NAE. If you did a replace on the controllers on the FX 70 now it is...
  7. Replies
    32
    Views
    977

    Authentication key is under lon netmgmt. Right...

    Authentication key is under lon netmgmt. Right click the lon network and select properties. Expand Lon Netmgmt. Authenticate should be set to false. Authentication key on mine is all FF FF FF FF...
  8. Replies
    14
    Views
    417

    What's the busy time in your JACE? What type of...

    What's the busy time in your JACE? What type of bindings did you setup Normal, Reliable, Critical (that's from memory may have left some out). Reliable and Critical will have a lot more traffic. Is...
  9. Replies
    3
    Views
    247

    I had a similar issue. I ended up using open...

    I had a similar issue. I ended up using open relay. It uses the IP address of the JACE to authenticate on the mail server so you don't need a user name or password. Works great and no password...
  10. Replies
    5
    Views
    290

    You also have to taggle the out of service points...

    You also have to taggle the out of service points for the particular points you want to control via the BAS.

    From the Trane Document:

    You can define the amount of control that the BAS system...
  11. Replies
    11
    Views
    533

    If you have a JAR file loaded on a JACE that is...

    If you have a JAR file loaded on a JACE that is not in the modules folder of that installation then the software manager will tell you that it is not available locally. If you are 100% certain that...
  12. Replies
    14
    Views
    417

    If there are any LON bindings that would be a...

    If there are any LON bindings that would be a good thing to know. Not sure how to find that out in an NAE but you would look at the LON network wire sheet of a JACE. Do not recommission any of the...
  13. Replies
    3
    Views
    255

    there is an example on the JCI whatspossible...

    there is an example on the JCI whatspossible website of using these. I think Greg Wilmer posted it.
  14. Replies
    10
    Views
    503

    Awesome. Thanks!

    Awesome. Thanks!
  15. Replies
    10
    Views
    503

    AWESOME! I will say after talking to 3...

    AWESOME!

    I will say after talking to 3 different schneider electric folks in different states and two 888 numbers later.....I still have no one that can or will help me. Software would be GREAT!...
  16. Replies
    10
    Views
    503

    While our service tech was there I had him look...

    While our service tech was there I had him look at the lights. The yellow (rx) light was blinking rapidly like it was getting data. The green Tx light was blinking like once a second or maybe...
  17. Replies
    10
    Views
    503

    PEM 1 Controller

    I am supposed to look at a PEM 1 controller tomorrow. I know it has an ASD bus but is this proprietary to Invensys? Is there any software that I can use to look at the controller?

    It seems this...
  18. Replies
    7
    Views
    269

    You see the entire network using Rover? Go to the...

    You see the entire network using Rover? Go to the Lon Utilities Manager in the JACE. Set the command to Identify and set the SubCommand to Service Pin and press Execute. Go to any lon controller...
  19. Replies
    11
    Views
    752

    Yellow means the device is down. Orange meas the...

    Yellow means the device is down. Orange meas the device or point is in a fault condition. Either way you are not communicating with the units/points that are in this color. If they "blink" in and...
  20. Replies
    11
    Views
    752

    I would have a look at the bacnet device manager....

    I would have a look at the bacnet device manager. See if the problem units are in yellow which could indicate a communication issue. Also, sometimes a JACE reboot will clear up some things,...
  21. Replies
    11
    Views
    314

    While I agree 100% that it is TAB's function to...

    While I agree 100% that it is TAB's function to enter this data into the boxes, I am stuck doing this most of the time for TAB. Last job I sat for two days and opened boxes to max/min flow and input...
  22. Replies
    11
    Views
    314

    I see that point scrool. So if the balancer...

    I see that point scrool. So if the balancer tells me the box is flowing 300 cfm and the box is reporting 210 cfm how do I know what value to make the gain?
  23. Replies
    11
    Views
    314

    They do show up. The has to be a point somewhere...

    They do show up. The has to be a point somewhere to enter the actual flow readings from a flow hood so the box can calibrate itself and adjust the K factor. So if the box is reporting 340 cfm and...
  24. Replies
    11
    Views
    314

    I looked for it on trane website but didn't see...

    I looked for it on trane website but didn't see it.
  25. Replies
    11
    Views
    314

    UC 400 VAV Balancing in Niagara

    I've got some new Trane VAV boxes with the UC 400 controller in them. I've got the Tracer TU Balancing guide but I don't have Tracer TU. I've found most of the points that TU talks about but I...