Good day Noskilltech, kontrolthis, TommyC11, Thanks for offers to test! Indeed, I will certainly keep you all in mind should we need additional testers. Cheers, Sam
S2sam, Not sure that we could qualify as a beta test site but we do support multiple N2 bus customers. Please give us a sneak peek as soon as you can !!! Thanks...
Yes likewise. Thanks
Originally Posted by s2sam Good day Cagey, Sadly, I cannot give you too many details just yet, as the project has not yet officially started (currently 3 ahead of this one). What I can say is that we have three different approaches that we will be evaluating/testing to see what works best... If all goes well, then the solution/variation would be applicable to non FX Users too. I will report back once I have more concrete information, but like I said, it will be a number of months yet. Cheers, Sam Let us know if you need beta testers.
Originally Posted by Cagey57 s2sam, Now you have my attention ! I really, Really, REALLY, want to know what you have in the works. Email me when you have something to share, Please ! A driver ? An interface ? What ???? I know, it will be a few month but I don't want to wait. Thanks Good day Cagey, Sadly, I cannot give you too many details just yet, as the project has not yet officially started (currently 3 ahead of this one). What I can say is that we have three different approaches that we will be evaluating/testing to see what works best... If all goes well, then the solution/variation would be applicable to non FX Users too. I will report back once I have more concrete information, but like I said, it will be a number of months yet. Cheers, Sam
s2sam, Now you have my attention ! I really, Really, REALLY, want to know what you have in the works. Email me when you have something to share, Please ! A driver ? An interface ? What ???? I know, it will be a few month but I don't want to wait. Thanks
Originally Posted by kontrolthis Got it. Thank you for the info. Has anyone found a third party work around to do the same? Good day KontrolThis, Stay tuned... We have something in the works for one of our customers. Sadly, it will be a few months before I will have additional info/results that I can post. Cheers, Sam
Unplug the N2 trunk from the FX60 and plug it into this http://s2innovations.com/s2usb485-interface now scan and upload with HVACpro. Kind of a pita but its the easiest thing to do.
Got it. Thank you for the info. Has anyone found a third party work around to do the same?
Code No. LIT-12011149 Issued August 2, 2011 Serial Tunnel and HVAC Pro Due to inconsistent behavior between HV AC Pro and the Serial Tunnel Service, HVAC Pro downloads are not supported. Serial Tunnel and GX 9100 Programming Tool Due to inconsistent behavior between GX 9100 Programming Tool and the Serial Tunnel Service, GX 9100 downloads are not supported.
Sorry, I should have clarified. My intent was to reprogram or commission a UNT hanging on an FX60. I know with our NAE's it's possible with tools, just looking to do the same with the Jace. I did come across an older thread that mentions needing to disable the bus then tunnel through to upload and download. This thread is 5 years old though. Didn't know if anything has changed good or bad to support this?
You can use the bacnet routing fuction if youre using the pcg controllers. It is also possible with the old legacy fx controllers too, bacnet and n2 both work. Its painful with the fx n2 controllers though.
Sorry, I forgot. HVAC Pro and GX 9100 are not supported. It is mentioned in the Workbench procedure.
Are you asking about N2 Tunneling? I think it requires an upgrade to the license. Here is a good discussion about it... http://hvac-talk.com/vbb/showthread....0-n2-tunneling.
Programming and commissioning through FX-60 Hey guys, is there a version of the commissioning software that would allow us to upload, download, commission, etc.. Unt's or Vav's through an FX front end? Also would this allow us to do so remotely with certain ports open? Thanks