Originally Posted by t527ed good thing you gave them CO detectors......... I hear ya! he's good for 20 yrs!
Originally Posted by actoken next day.........lennox out...............carrier in! good thing you gave them CO detectors.........
Originally Posted by diazmatx I hope you sold them a new unit bro! next day.........lennox out...............carrier in!
I hope you sold them a new unit bro!
Originally Posted by auwing Carbon monoxide detector would be a good thing CO detectors *should* be mandatory wherever combustion appliances exist. It'd be one of the few codes I'd be in support of.
Originally Posted by tincup51 Home owner should call the other contractor and let them know how big of idiots they are. I wish i was there to give my 2 cents also! now they have 2 co2 detectors!part of sale of new heater! i wanted the techs name,so i will never hire that idiot[s]
Carbon monoxide detector would be a good thing
Originally Posted by actoken Got this call late last night,scared the bejesus out of this poor homeowner. i said"you will die, ihave to disconnect the unit"![im very blunt when tired]I thought he was gonna punch me when i told him how much a new one costs!Long story short i meet the crew down there to cut it out to show him!He was very understanding when he saw that!Then he admitted "you know,weve been having head aches off&on since last winter"! sad part,we were the 2nd co out this winter!they made sure there sticker was all over the unit!YIKES!!!!!!!!!!!!! Home owner should call the other contractor and let them know how big of idiots they are.
Duct tape can fix anything..... well maybe not
Originally Posted by supertek65 was this easy to find?? could the other tech missed it? what made you inspect the heat exchanger on the service call? was the gas pressure too high or the delta t too high? why did it crack? its manditory to inspect ht ex on ALL service calls , ive seen em bust in 2 yrs!
was this easy to find?? could the other tech missed it? what made you inspect the heat exchanger on the service call? was the gas pressure too high or the delta t too high? why did it crack?
Originally Posted by above-par The new heat excangers are a pain to install. they've gone to tubular type ........stainless steel..........too expensive to replace!costs little less than a new unit!
a lil peel and seal will fix er right up
The new heat excangers are a pain to install. they've gone to tubular type
Head aches last winter-Thats insane
Originally Posted by Milk man Is that out of a GCS16H? What was the initial complaint and symptoms? no heat was the call!bad induce motor was the prob,till i found this! lennox gas pak
i got some tape that will fix that ha
It is an old lennox helical heat exchanger, I see quite a few of those in my area. most(if not all) are in that condition.
why can't you "patch it up" always feel bad when i have to shut one down at night
It looks like a HX from a Lennox packaged unit. If so the HX does not run under positive pressure.