sraburne
06-22-2007, 05:17 PM
I Had a upflow furnace blower not running call about 30 days ago 5/23/07. Found the blower motor hot and running slow' with high amps. Tested the run capacitor,tested bad,rated at 10mfd getting 0/open. Oh ya' the filter was plugged solid, After installing new cap and filter, the motor ran fine.
Today found blower not running. Tested the new run capacitor,only getting 2.5 mfd's. Suggest replacing the motor or I would replace the run Cap under warranty and give Bid to replace blower motor. My question is why did the capacitor fail? other than I installed a bad run cap.
Thanks for your time.
Steve::confused:
Today found blower not running. Tested the new run capacitor,only getting 2.5 mfd's. Suggest replacing the motor or I would replace the run Cap under warranty and give Bid to replace blower motor. My question is why did the capacitor fail? other than I installed a bad run cap.
Thanks for your time.
Steve::confused: