View Full Version : RJ Traush Rack
engineerdave
01-20-2007, 01:42 PM
Went to look at a prospective new account yesterday. Split temp rack, R-22. Mfr lable says P.O.E. oil? Guess I must've missed that thread....?
innovator
01-20-2007, 10:05 PM
I dont think I saw that thread either.
Trausch rack= bad purchase. I didnt know they ever made racks.. pirates.
engineerdave
01-20-2007, 10:08 PM
I never heard of them until yesterday. Didn't know we run P.O.E. with 22 until yesterday either. What am I getting myself into?
innovator
01-20-2007, 10:19 PM
I always removed the factory POE charge and replaced with Zerol 150 when replacing any R-22 machine... I guess I was wasting my time!
Is it a true RJ trausch built rack? If so this is a first for me... do you know if they really charged with POE????
engineerdave
01-20-2007, 10:24 PM
I only know what the stickers on the dashboard said. We haven't picked up that account yet, so no wrenches on the job. Mfr Date was 2001.
smilies
01-20-2007, 11:42 PM
Not common, but it's out there. When doing conversions from 22 to 404 we change to POE first and run it for a month. Does a job of cleaning everything and plugging oil seperators! But they all run fine with 22, it's just a cost thing.
AB-150 is about $20
POE is about $50
engineerdave
01-21-2007, 01:42 AM
This Rack is six years old and has had compressors replaced. One MT unit was off on Oil Fail when I was there, but I did not diagnose. (Under pretty strict marchin' orders....:o ) What can I expect to see if P.O.E. and AB are mixed?